1.5MW/3MWh AC+DC BESS Container (Grid-tie and off-grid)
This solution provides a utility-level AC+DC all-in-one container, ideal for microgrid grid-tie and off-grid scenarios. It is also suitable for utility-scale applications.



Category | Details |
System Model | VF1500-3000-USCA-690 |
DC Parameters | |
Battery Cell Type | LFP/306Ah |
Battery Capacity at DC Side (BOL) | 3008kWh |
Rated Voltage | 12288V |
AC Parameters | |
Rated Capacity | 1504KVA |
PCS Module Quantity | 8 |
Rated Voltage | AC 690V |
Voltage Range | -15%-10% |
Max. Current Harmonic Distortion Rate | < 3% (at nominal power) |
Power Factor | ±1 |
Rated Frequency | 50/60Hz |
General Parameters | |
Battery and PCS Container Size (WHD) | 6058*2896*2438mm |
Battery and PCS Container Weight | 32,000kg |
IP Level | IP54 |
Operating Temperature | -20℃ - 50℃ (>45℃ derating) |
Relative Humidity | 5%-95% |
Highest Working Altitude | 2000m |
Battery Temperature Control Method | Liquid cooling |
PCS Cooling Method | Forced air cooling |
Fire Protection System | Aerosol, smoke and temperature detector |
Compliance Standard | System UL9540 (Canada & US) Inverter UL1741 (Canada & US) Battery UL9540A, UL1973 (Canada & US) |